Calorifiers
Action: Inspect calorifier internally by removing the inspection hatch or using a boroscope and clean by draining the vessel. The frequency of inspection and cleaning should be subject to the findings and increased or decreased based on conditions recorded
Frequency: Annually, or as indicated by the rate of fouling
Action: Where there is no inspection hatch, purge any debris in the base of the calorifier to a suitable drain. Collect the initial flush from the base of hot water heaters to inspect clarity, quantity of debris, and temperature
Frequency: Annually, but may be increased as indicated by the risk assessment or result of inspection findings
Action: Check calorifier flow temperatures (thermostat settings should modulate as close to 60 °C as practicable without going below 60 °C) Check calorifier return temperatures (not below 50 °C).
Frequency: Monthly
Cold water tanks
Action: Inspect cold water storage tanks and carry out remedial work where necessary.
Frequency: Annually.
Action: Check the tank water temperature remote from the ball valve and the incoming mains temperature. Record the maximum temperatures of the stored and supply water recorded by fixed maximum/minimum thermometers where fitted.
Frequency: Annually (Summer) or as indicated by the temperature profiling.
Shower head maintenance
Action: Dismantle, clean and descale removable parts, heads, inserts and hoses where fitted.
Frequency: Quarterly or as indicated by the rate of fouling or other risk factors, eg areas with high risk patients.
Piping & pipework
Action: Consideration should be given to removing infrequently used showers, taps and any associated equipment that uses water. If removed, any redundant supply pipework should be cut back as far as possible to a common supply.
Frequency: Adhoc
Outlets & Spray taps
Action: Dismantle, clean and descale removable parts, heads, inserts and hoses where fitted.
Frequency: Quarterly or as indicated by the rate of fouling or other risk factors, eg areas with high risk patients.
Water System Maintenance Services
Reef is backed by our cloud based water management software.
We can treat your water with our Orca and Ray units, we can test your water with our Tetras cloud based water management solution and now we can engineer out your issues with our software backed water engineering service.
At the heart of this service is our software. Through our online portal you can now track remedial actions, monitor assets and holistically gauge the successes of our engineered solutions. In this way we aim to guide you through the process of ensuring compliant and safe water.
Trust in our accredited and experienced water engineers.
Get on top of your water compliance with Reef, Remotely login to dedicated client portal to track your sites water systems and gain an understanding of the impact of our engineered solutions.
Download our Reef brochure
Simply fill in the form below to download our brochure.