High-flow
Copper and silver ionisation for large buildings and campuses.
- Treats 150–500 L/min on 4 inch pipework, up to 9 bar
- Ultrasonic flow measurement, dosing down to parts per billion
- Live status over LAN or LTE, BMS compatible
- Electrode pod serviced on site in one visit
Sized for large buildings and campuses, the top of the range.
Headroom for mains-fed commercial systems.
Fits inline on large commercial pipework.
Live status and settings changed without a visit.
For very high flow rates.Scaled to the site.
Copper and silver ionisation that keeps Legionella, Pseudomonas and other harmful waterborne bacteria under control, from one wall-mounted unit.

For very high flow rates
Ray 03 treats 150 to 500 L/min, for large hospitals, universities, airports and industrial sites.

Twelve electrodes in one pod
Ten copper bars and two silver bars in a single pod carry the ion output that high flows need.

Scale to any site
Run several Ray 03 units side by side to treat hundreds of thousands of litres per hour, adding capacity as the site grows.
Water in at the top. Protected water out at the bottom.
Ray 03 is mounted vertically and treats water as it passes through. Follow one litre through the unit.
-
Inlet
Water enters from the top.
Ray 03 fits inline on 4 inch pipework and is mounted vertically, so water always flows top to bottom.
4 in150–500 L/min≤ 9 bar≤ 30 °C -
Measure
Flow is measured continuously.
An ultrasonic sensor reads the flow and the PLC in the control panel matches ion output to it. No flow, no dosing.
Ultrasonic sensingPLC dosing controlLAN · LTEBMS compatible -
Ionise
Copper and silver ions are released.
Low-voltage DC passes across ten copper bars and two silver bars in the pod, releasing Cu²⁺ and Ag⁺ ions. Together they control Legionella, Pseudomonas and other disease-causing bacteria.
10 × Cu bars2 × Ag bars48 V · 9.5 A max12 V · 2.5 A max -
Service
Serviced in place.
With the system on by-pass, the pod lifts out between its two unions so the bars can be inspected, cleaned or replaced.
Pod lifts out wholeNo specialist contractor -
Outlet
Protection travels with the water.
Ions leave with the water and reach the whole system, including little-used outlets.
Whole-system residualNo COSHH chemicals
Twelve bars in one pod. Ten copper, two silver.
The copper and silver bars set the ion output that high flows need. Scroll to see inside the Ray 03 pod.
- 01The electrode podThe pod sits inline and lifts out as one piece.
- 02Sleeve offWith the outer sleeve removed, the insert and its bars are exposed.
- 03Ten copper, two silverTwelve bars on one insert, for the ion output of a high-flow system.
Engineer-friendly design.
Plug and play. Keyed connectors, from the unit to the panel.
Simple to service. The pod comes out between two unions.
The unit in detail.
Select a point on the drawing to see its size and material.
Hydraulics and electrodes
- Flow rate
- 150–500 L/min
- Pipe size
- 4 in
- Max operating pressure
- 9 bar
- Electrode bars
- 10 copper / 2 silver
- Weight of electrodes
- Cu 0.620 kgAg 0.340 kg per bar
- Copper and silver purity
- 99.99 %BPR compliant
- Cold water applications
- 30 °C max
- Main unit
- 1558 × 272 × 208 mmL × W × H
- Control panel
- 500 × 400 × 200 mmH × W × D
- Unit weight
- 17 kg
- Control panel weight
- 12.5 kg
Control and electronics
- Flow sensing
- Ultrasonic flow sensor
- Dosing control
- PLC
- Voltage and power
- 230 V AC at 5 A max
- Ionisation output
- Cu 48 V at 9.5 A maxAg 12 V at 2.5 A max
- Remote access
- LAN and LTEBMS compatible
- Mounting
- Wall, backboard and panel
The ultrasonic sensor measures flow continuously and the PLC matches copper and silver output to it; status and faults report over LAN or LTE.
Sized for the largest sites. Where Ray 03 fits.
For sites with 150 to 500 L/min of flow on 4 inch pipework.
Large hotels and resorts
Hundreds of rooms, kitchens and leisure on one supply.
Universities and campuses
Many buildings and long runs from one plant room.
Airports and industrial sites
High, variable demand around the clock.
Large hospitals
Whole estates where water safety is critical.
Every Ray 03 reports to tetras.
The control panel connects over LAN or LTE, so whoever is responsible for the water system can see what the unit is doing without a site visit.
Flow, last 7 days
Technical data
Three units, sized by flow.
The same fields in the same order for every model. Ray 03 covers the top of the range. Each model is modular, so several units can run side by side as a site grows.
| Specification | |||
|---|---|---|---|
| Hydraulics | |||
| Flow rate | 1–22 L/min | 5–150 L/min | 150–500 L/min |
| Pipe size | 1½ in | 2 in | 4 in |
| Max operating pressure | 6 bar | 9 bar | 9 bar |
| Max water temperature | 30 °C | 30 °C | 30 °C |
| Electrodes | |||
| Silver bars | 2 × 0.021 kg | 2 × 0.340 kg | 2 × 0.340 kg |
| Copper bars | 2 × 0.201 kg | 2 × 0.620 kg | 10 × 0.620 kg |
| Electrode material | BPR-compliant Cu, Ag | BPR-compliant Cu, Ag | BPR-compliant Cu, Ag |
| Control | |||
| Flow sensing | Flow switch | Ultrasonic | Ultrasonic |
| Dosing control | Digital control box | PLC | PLC |
| Remote monitoring | Not available | LAN and LTE | LAN and LTE |
| BMS integration | Not available | Yes | Yes |
| Electrical | |||
| Power supply | 230 V AC, 5 A max | 230 V AC, 5 A max | 230 V AC, 5 A max |
| Copper output | 24 V, 2 A max (shared) | 48 V, 3 A max | 48 V, 9.5 A max |
| Silver output | 24 V, 2 A max (shared) | 12 V, 0.9 A max | 12 V, 2.5 A max |
| Physical | |||
| Main unit, L × W × H | 432 × 130 × 141 mm | 1040 × 190 × 125 mm | 1558 × 272 × 208 mm |
| Control panel, H × W × D | Compact control box | 500 × 400 × 200 mm | 500 × 400 × 200 mm |
| Weight | 2 kg | 8 kg + 12.5 kg panel | 17 kg + 12.5 kg panel |
| Application | |||
| Designed for | Low flow. A flow switch gives precise dosing at low flows. | Site-wide treatment. Ultrasonic measurement doses down to parts per billion. | Very high flow, for large buildings and campuses. |
| Typical sites | Schools, food preparation, hospital wards, swimming pools | Hotels, offices, leisure and sports centres, mid-sized hospitals | Large hospitals, universities, airports, industrial sites |
Explore other Ray products.
Request more information. We'll come back to you.
Tell us what you need and the right person will reply.
Prefer to talk? Call +44 (0)1525 854 111 or email sales@proeconomy.com